Deemed-to-Satisfy Provision · NCC 2022 Volume One

F2D4 Floor wastes

Part F2 Wet areas and overflow protection · NCC 2019: SA F1.11, F1.11

Open F2D4 on NCC Online ↗
Varied in SA. Check the variation for your state.

(1) In a Class 2 or 3 building or Class 4 part of a building, a bathroom or laundry located at any level above a sole-occupancy unit or public space must have a floor waste.

(2) Where a floor waste is installed—

the minimum continuous fall of a floor plane to the waste must be 1:80; and

the maximum continuous fall of a floor plane to the waste must be 1:50.

Same wording in NCC 2025 Volume One. See NCC 2025 Volume One F2D4.
Can't meet F2D4? A Performance Solution must meet the Performance Requirements it satisfies: F2P1, F2P2. Start a Performance Solution →

State and territory variations all clauses side by side →