South Australia variation · NCC 2022 Volume One

SA F2D4 Provision of floor wastes

Part F2 Wet areas and overflow protection · varies F2D4 Floor wastes

Open on NCC Online ↗

Delete clause F2D4 and insert SA F2D4 as follows:

(1) A wet area provided with a vessel in accordance with F4D2, F4D4 and F4D5 must have the floor graded to a floor waste to permit drainage of water.

(2) With the exception of a bathroom or laundry located at any level above a sole-occupancy unit or public space in a Class 2 or 3 building or Class 4 part of a building, a floor need not be graded to a floor waste in accordance with (1) if—

all vessels in the wet area are provided with in-built overflow protection or have permanent open trapped connection to the plumbing and drainage system (such as a WC pan); or

the vessel is a clinical hand washing basin in a Class 9c building; or

the floor waste is provided solely for the connection of plumbing fixtures and all vessel in the wet area are provided with in-built overflow protection or have permanent open trapped connection to the plumbing and drainage system (such as a WC pan).

(3) The fall of the floor surface to a floor waste required by (1) or (2) must be in accordance with F2D4(2).

Same wording in NCC 2025 Volume One. See NCC 2025 Volume One SA F2D4.

The national clause