Deemed-to-Satisfy Provision · NCC 2022 Volume One

F4D12 Accessible adult change facilities

Part F4 Sanitary and other facilities · NCC 2019: F2.9

Open F4D12 on NCC Online ↗

(1) One unisex accessible adult change facility must be provided in an accessible part of a—

Class 6 building that is a shopping centre having a design occupancy of not less than 3,500 people, calculated on the basis of the floor area and containing a minimum of 2 sole-occupancy units; and

Class 9b sports venue or the like that—

has a design occupancy of not less than 35,000 spectators; or

contains a swimming pool that has a perimeter of not less than 70 m and that is required by D4D2 to be accessible; and

museum, art gallery or the like having a design occupancy of not less than 1,500 patrons; and

theatre or the like having a design occupancy of not less than 1,500 patrons; and

passenger use area of an airport terminal building within an airport that accepts domestic and/or international flights that are public transport services as defined in the Disability Standards for Accessible Public Transport 2002.

(2) Accessible adult change facilities required by (1)—

must be constructed in accordance with Specification 27; and

cannot be combined with another sanitary compartment.

(3) For the purposes of (1), design occupancy must be calculated in accordance with D2D18, but excluding any area that—

can only be accessed by staff, employees, contractors, maintenance personnel and the like; or

is subject to an exemption under D4D5.

Same wording in NCC 2025 Volume One. See NCC 2025 Volume One F4D12.