Performance Requirement · NCC 2022 Volume One

F7P2 Sound transmission through walls

Part F7 Sound transmission and insulation · NCC 2019: NT FP5.2, FP5.2

Open F7P2 on NCC Online ↗
Varied in NT. Check the variation for your state.

A wall, including services and their penetrations, must minimise the transmission of sound such that—

for airborne sound—

a wall separating sole-occupancy units has a weighted standardised level difference with spectrum adaptation term (DnT,w + Ctr) not less than 45; and

a wall separating a sole-occupancy unit from a plant room, lift shaft, stairway, public corridor, public lobby, or the like, or parts of a different classification, has a weighted standardised level difference (DnT,w) not less than 45; and

any door assembly located in a wall that separates a sole-occupancy unit from a stairway, public corridor, public lobby, or the like, has a weighted standardised level difference (DnT,w) not less than 25; and

for impact generated sound, a wall must have sufficient sound insulation to prevent illness or loss of amenity to the occupants if the wall separates—

a bathroom, sanitary compartment, laundry or kitchen in one sole-occupancy unit from a habitable room (other than a kitchen) in an adjoining sole-occupancy unit; or

a sole-occupancy unit from a plant room or lift shaft.

Applications

F7P2 only applies to a Class 2 or 3 building.

Same wording in NCC 2025 Volume One. See NCC 2025 Volume One F7P2.

State and territory variations all clauses side by side →