F7P2 Sound transmission through walls
Part F7 Sound transmission and insulation · NCC 2019: NT FP5.2, FP5.2
A wall, including services and their penetrations, must minimise the transmission of sound such that—
for airborne sound—
a wall separating sole-occupancy units has a weighted standardised level difference with spectrum adaptation term (DnT,w + Ctr) not less than 45; and
a wall separating a sole-occupancy unit from a plant room, lift shaft, stairway, public corridor, public lobby, or the like, or parts of a different classification, has a weighted standardised level difference (DnT,w) not less than 45; and
any door assembly located in a wall that separates a sole-occupancy unit from a stairway, public corridor, public lobby, or the like, has a weighted standardised level difference (DnT,w) not less than 25; and
for impact generated sound, a wall must have sufficient sound insulation to prevent illness or loss of amenity to the occupants if the wall separates—
a bathroom, sanitary compartment, laundry or kitchen in one sole-occupancy unit from a habitable room (other than a kitchen) in an adjoining sole-occupancy unit; or
a sole-occupancy unit from a plant room or lift shaft.
Applications
F7P2 only applies to a Class 2 or 3 building.