Performance Requirement · NCC 2022 Volume One
F7P3 Sound transmission through floors in a residential care building
Part F7 Sound transmission and insulation · NCC 2019: NT FP5.3, FP5.4
Varied in NT. Check the variation for your state.
A floor separating sole-occupancy units must minimise the transmission of airborne and impact generated sound such that the separating floor, including the effect of services and their penetrations, has—
a weighted standardised level difference (DnT,w) not less than 40 for airborne sound; and
a weighted standardised impact sound pressure level (LnT,w) not more than 62 for impact generated sound.
Applications
F7P3 only applies to a Class 9c building.
Same wording in NCC 2025 Volume One. See NCC 2025 Volume One F7P3.