Performance Requirement · NCC 2022 Volume One

F7P3 Sound transmission through floors in a residential care building

Part F7 Sound transmission and insulation · NCC 2019: NT FP5.3, FP5.4

Open F7P3 on NCC Online ↗
Varied in NT. Check the variation for your state.

A floor separating sole-occupancy units must minimise the transmission of airborne and impact generated sound such that the separating floor, including the effect of services and their penetrations, has—

a weighted standardised level difference (DnT,w) not less than 40 for airborne sound; and

a weighted standardised impact sound pressure level (LnT,w) not more than 62 for impact generated sound.

Applications

F7P3 only applies to a Class 9c building.

Same wording in NCC 2025 Volume One. See NCC 2025 Volume One F7P3.

State and territory variations all clauses side by side →