G5P2 Additional bushfire requirements for certain Class 9 buildings
Part G5 Construction in bushfire prone areas
A building that is constructed in a designated bushfire prone area and occupied by people who may be unable to readily evacuate the building prior to a bushfire must, to the degree necessary—
reduce the risk of an untenable indoor environment for occupants during a bushfire event, appropriate to the—
location of the building relative to fire hazards, including—
classified vegetation; and
adjacent buildings, structures and movable objects; and
carparking areas and allotment boundaries; and
other combustible materials; and
number of occupants to be accommodated within the building; and
intensity of bushfire attack on the building; and
duration of occupancy; and
intensity of potential consequential fires; and
occupant tenability within the building before, during and after the bushfire event; and
combined effects of structural, fire exposure and other effects to which the building may reasonably be subjected; and
provision of fire fighting equipment and water supply to facilitate protection of the building; and
be provided with vehicular access to the site to enable firefighting and emergency personnel to defend or evacuate the building; and
have access to a sufficient supply of water for firefighting purposes on the site; and
provide safe access within the site to the building (including carparking areas), as well as safe egress after the bushfire event.
Applications
G5P2 applies to the following buildings located in a designated bushfire prone area—
a Class 9a health-care building; and
a Class 9b—
early childhood centre; and
primary or secondary school; and
a Class 9c residential care building.
Notes
G5P2 does not guarantee the safety of building occupants or the maintenance of tenable conditions within a building during a bushfire event.