New South Wales variation · NCC 2022 Volume One

NSW G5P2 Additional bushfire requirements for Class 9 buildings that are a special fire protection purpose

Part G5 Construction in bushfire prone areas · varies G5P2 Additional bushfire requirements for certain Class 9 buildings

Open on NCC Online ↗

Delete clause G5P2 and insert NSW G5P2 as follows:

A building that is constructed in a designated bushfire prone area and occupied by people who may be unable to readily evacuate the building prior to a bushfire must, to the degree necessary—

reduce the risk of an untenable indoor environment for occupants during a bushfire event, appropriate to the—

location of the building relative to fire hazards, including—

classified vegetation; and

adjacent buildings, structures and movable objects; and

carparking areas and allotment boundaries; and

other combustible materials; and

number of occupants to be accommodated within the building; and

intensity of bushfire attack on the building; and

duration of occupancy; and

intensity of potential consequential fires; and

occupant tenability within the building before, during and after the bushfire event; and

combined effects of structural, fire exposure and other effects to which the building may reasonably be subjected; and

provision of fire fighting equipment and water supply to facilitate protection of the building; and

be provided with vehicular access to the site to enable firefighting and emergency personnel to defend or evacuate the building; and

have access to a sufficient supply of water for firefighting purposes on the site; and

provide safe access within the site to the building (including carparking areas), as well as safe egress after the bushfire event.

Applications

NSW G5P2 applies to a Class 9 building that is a special fire protection purpose located in a designated bushfire prone area.

Notes

NSW G5P2 does not guarantee the safety of building occupants or the maintenance of tenable conditions within a building during a bushfire event.

Changed in NCC 2025. See NCC 2025 Volume One NSW G5P2, or show what changed.

Delete clause G5P2 and insert NSW G5P2 as follows: A Except as amended by Planning for Bush Fire Protection, a building that is constructed in a designated bushfire prone area … of tenable conditions within a building during a bushfire event.

Removed words are struck through; added words are highlighted. Comparison of the text only.