New South Wales variation · NCC 2022 Volume One

NSW J1V2 Green star

NSW Part J1 Energy efficiency performance requirements · varies J1V2 Green Star

Open on NCC Online ↗

(1) For a Class 3, 5, 6, 7, 8 or 9 building, compliance with NSW J1P1 is verified when—

the building complies with the simulation requirements, and is registered, for a Green Star – Design & As-Built or Green Star Buildings rating; and

the annual greenhouse gas emissions of the proposed building are less than 90% of the annual greenhouse gas emissions of the reference building; and

in the proposed building, a thermal comfort level of between a Predicted Mean Vote of -1 to +1 is achieved across not less than 95% of the floor area of all occupied zones for not less than 98% of the annual hours of operation of the building; and

the building complies with the additional requirements in Specification 33.

(2) The calculation method used for (1) must comply with ANSI/ASHRAE Standard 140.

Changed in NCC 2025. See NCC 2025 Volume One NSW J1V2, or show what changed.

Insert NSW clause J1V2 in clause J1V2 as follows: (1) For a Class 3, 5, 6, 7, 8 or … complies with the simulation requirements, and is registered, for a Green Star – Design & As-Built or Green Star Buildings rating; and the annual greenhouse gas emissions … method used for (1) must comply with ANSI/ASHRAE Standard 140.

Removed words are struck through; added words are highlighted. Comparison of the text only.