Verification Method · NCC 2022 Volume One

J1V5 Verification using a reference building for a Class 2 sole-occupancy unit

Part J1 Energy efficiency performance requirements

Open J1V5 on NCC Online ↗

(1) Compliance with J1P2 is verified when each Class 2 sole-occupancy unit of a proposed building—

in climate zones 3, 4, 5, 6, 7 and 8, has a heating load less than or equal to—

that of a reference building; and

120% of J1P2(1); and

in climate zones 1, 2, 3, 4 and 5, has a cooling load less than or equal to—

that of a reference building; and

120% of J1P2(2); and

complies with the additional requirements in Specifications 33 and 45 as applicable.

(2) Compliance with J1P3 is determined when the energy value of the domestic services, including all centralised domestic services infrastructure, of a proposed building is less than that of a reference building when—

each sole-occupancy unit of a reference building has—

a 3-star ducted air-to-air heat pump, rated under the 2019 GEMS determination, heating all spaces that are provided with heating; and

a 3-star ducted heat pump, rated under the 2019 GEMS determination, cooling all spaces that are provided with cooling; and

a 5-star instantaneous gas water heater, rated under the 2017 GEMS determination, providing all domestic heated water; and

a lighting power density of 4 W/m2 serving all internal spaces that are provided with artificial lighting; and

the proposed building and a reference building comply with the additional requirements in Specifications 33 and 45 as applicable.

(3) The calculation method used for (1) and (2) must—

comply with ANSI/ASHRAE Standard 140; and

not be house energy rating software.

Not in NCC 2025. No J1V5 in NCC 2025 Volume One.

Clauses referred to

Defined terms used