J1V5 Verification using a reference building for a Class 2 sole-occupancy unit
Part J1 Energy efficiency performance requirements
(1) Compliance with J1P2 is verified when each Class 2 sole-occupancy unit of a proposed building—
in climate zones 3, 4, 5, 6, 7 and 8, has a heating load less than or equal to—
that of a reference building; and
120% of J1P2(1); and
in climate zones 1, 2, 3, 4 and 5, has a cooling load less than or equal to—
that of a reference building; and
120% of J1P2(2); and
complies with the additional requirements in Specifications 33 and 45 as applicable.
(2) Compliance with J1P3 is determined when the energy value of the domestic services, including all centralised domestic services infrastructure, of a proposed building is less than that of a reference building when—
each sole-occupancy unit of a reference building has—
a 3-star ducted air-to-air heat pump, rated under the 2019 GEMS determination, heating all spaces that are provided with heating; and
a 3-star ducted heat pump, rated under the 2019 GEMS determination, cooling all spaces that are provided with cooling; and
a 5-star instantaneous gas water heater, rated under the 2017 GEMS determination, providing all domestic heated water; and
a lighting power density of 4 W/m2 serving all internal spaces that are provided with artificial lighting; and
the proposed building and a reference building comply with the additional requirements in Specifications 33 and 45 as applicable.
(3) The calculation method used for (1) and (2) must—
comply with ANSI/ASHRAE Standard 140; and
not be house energy rating software.
Clauses referred to
- J1P2 Thermal performance of a sole-occupancy unit of a Class 2 building or a Class 4 part of a building
- J1P3 Energy usage of a sole-occupancy unit of a Class 2 building or a Class 4 part of a building