Deemed-to-Satisfy Provision · NCC 2022 Volume One

J7D3 Artificial lighting

Part J7 Artificial lighting and power · NCC 2019: J6.2

Open J7D3 on NCC Online ↗
Varied in NSW. Check the variation for your state.

(1) In a sole-occupancy unit of a Class 2 building or a Class 4 part of a building—

the lamp power density or illumination power density of artificial lighting must not exceed the allowance of—

5 W/m2 within a sole-occupancy unit; and

4 W/m2 on a verandah, balcony or the like attached to a sole-occupancy unit; and

the illumination power density allowance in (a) may be increased by dividing it by the illumination power density adjustment factor for a control device in Table J7D3b as applicable; and

when designing the lamp power density or illumination power density, the power of the proposed installation must be used rather than nominal allowances for exposed batten holders or luminaires; and

halogen lamps must be separately switched from fluorescent lamps.

(2) In a building other than a sole-occupancy unit of a Class 2 building or a Class 4 part of a building—

for artificial lighting, the aggregate design illumination power load must not exceed the sum of the allowances obtained by multiplying the area of each space by the maximum illumination power density in Table J7D3a; and

the aggregate design illumination power load in (a) is the sum of the design illumination power loads in each of the spaces served; and

where there are multiple lighting systems serving the same space, the design illumination power load for (b) is—

the total illumination power load of all systems; or

where a control system permits only one system to operate at a time based on the highest illumination power load; or determined by the formula— [formula] In the formula at (c)(ii)—

[formula] = the highest illumination power load; and

[formula] = the time for which the maximum illumination power load will occur, expressed as a percentage; and

[formula] = the predominant illumination power load.

(3) The requirements of (1) and (2) do not apply to the following:

Emergency lighting provided in accordance with Part E4.

Signage, display lighting within cabinets and display cases that are fixed in place.

Lighting for accommodation within the residential part of a detention centre.

A heater where the heater also emits light, such as in bathrooms.

Lighting of a specialist process nature such as in a surgical operating theatre, fume cupboard or clean workstation.

Lighting of performances such as theatrical or sporting.

Lighting for the permanent display and preservation of works of art or objects in a museum or gallery other than for retail sale, purchase or auction.

Lighting installed solely to provide photosynthetically active radiation for indoor plant growth on green walls and the like.

(4) For the purposes of Table J7D3b, the following control devices must comply with Specification 40:

Lighting timers.

Motion detectors.

Daylight sensors and dynamic lighting control devices.

Table J7D3a Maximum illumination power density

Space

Maximum illumination power density (W/m2)

Auditorium, church and public hall

8

Board room and conference room

5

Carpark - general

2

Carpark - entry zone (first 15 m of travel) during the daytime

11.5

Carpark - entry zone (next 4 m of travel) during the day

2.5

Carpark - entry zone (first 20 m of travel) during night time

2.5

Common rooms, spaces and corridors in a Class 2 building

4.5

Control room, switch room and the like - intermittent monitoring

3

Control room, switch room and the like - constant monitoring

4.5

Corridors

5

Courtroom

4.5

Dormitory of a Class 3 building used for sleeping only

3

Dormitory of a Class 3 building used for sleeping and study

4

Entry lobby from outside the building

9

Health-care - infants' and children's wards and emergency department

4

Health-care - examination room

4.5

Health-care - examination room in intensive care and high dependency ward

6

Health-care - all other patient care areas including wards and corridors

2.5

Kitchen and food preparation area

4

Laboratory - artificially lit to an ambient level of 400 lx or more

6

Library - stack and shelving area

2.5

Library - reading room and general areas

4.5

Lounge area for communal use in a Class 3 or 9c building

4.5

Museum and gallery - circulation, cleaning and service lighting

2.5

Office - artificially lit to an ambient level of 200 lx or more

4.5

Office - artificially lit to an ambient level of less than 200 lx

2.5

Plant room where an average of 160 lx vertical illuminance is required on a vertical panel such as in switch rooms

4

Plant rooms with a horizontal illuminance target of 80 lx

2

Restaurant, café, bar, hotel lounge and a space for the serving and consumption of food or drinks

14

Retail space including a museum and gallery whose purpose is the sale of objects

14

School - general purpose learning areas and tutorial rooms

4.5

Sole-occupancy unit of a Class 3 or 9c building

5

Storage

1.5

Service area, cleaner's room and the like

1.5

Toilet, locker room, staff room, rest room and the like

3

Wholesale storage area with a vertical illuminance target of 160 lx

4

Stairways, including fire-isolated stairways

2

Lift cars

3

Table Notes

In areas not listed above, the maximum illumination power density is—

for an illuminance not more than 80 lx, 2 W/m2; and

for an illuminance more than 80 lx and not more than 160 lx, 2.5 W/m2; and

for an illuminance more than 160 lx and not more than 240 lx, 3 W/m2; and

for an illuminance more than 240 lx and not more than 320 lx, 4.5 W/m2; and

for an illuminance more than 320 lx and not more than 400 lx, 6 W/m2; and

for an illuminance more than 400 lx and not more than 600 lx, 10 W/m2; and

for an illuminance more than 600 lx and not more than 800 lx, 11.5 W/m2.

For enclosed spaces with a Room Aspect Ratio of less than 1.5, the maximum illumination power density may be increased by dividing it by an adjustment factor for room aspect which is 0.5 + (Room Aspect Ratio/3).

The Room Aspect Ratio of the enclosed space is determined by the formula: A/(H x C), where—

A is the area of the enclosed space; and

H is the height of the space measured from the floor to the highest part of the ceiling; and

C is the perimeter of the enclosed space at floor level.

In addition to 2, the maximum illumination power density may be increased by dividing it by the illumination power density adjustment factor in Table J7D3b and Table J7D3c and where the control device is not installed to comply with J6D4.

Circulation spaces are included in the allowances listed in the Table.

Table J7D3b Illumination power density adjustment factor for a control device

Item Notes 1 and 2

Description

illumination power density adjustment factor

Motion detector

In a toilet or change room, other than a public toilet, in a Class 6 building

0.4

Motion detector

Where a group of light fittings serving less than 100 m2 is controlled by one or more detectors

0.6

Motion detector

Where a group of light fittings serving 100 m2 or more is controlled by one or more detectors

0.7

Programmable dimming system Note 3

Where not less than 75% of the area of a space is controlled by programmable dimmers

0.85

Fixed dimming Notes 3 and 4

All fittings with fixed dimming

Whichever is greater of (a) 0.5; or (b) 0.2+0.8L where L = the illuminance turndown for the fixed dimming.

Lumen depreciation dimming Note 3

All fittings with lumen depreciation dimming

0.85

Two stage sensor - equipped lights with minimum power of 30 % of peak power or less

Fire stairs and other spaces not used for regular transit

0.4

Two stage sensor - equipped lights with minimum power of 30% of peak power or less

Transitory spaces in regular use or in a carpark

0.7

Daylight sensor and dynamic lighting control device - dimmed or stepped switching of lights adjacent windows Notes 3 and 5

In a Class 5, 6, 7, 8 or 9b building or a Class 9a building, other than a ward area, where the lights are adjacent windows, other than roof lights, for a distance from the window equal to the depth of the floor to window head height

0.5 Note 3

Daylight sensor and dynamic lighting control device - dimmed or stepped switching of lights adjacent windows Notes 3 and 5

Se

Tables

Changed in NCC 2025. See NCC 2025 Volume One J7D3, or show what changed.

(1) In a sole-occupancy unit of a Class 2 building or a Class 4 part of a building — the lamp … switched from fluorescent lamps. (2) In a building other than a sole-occupancy unit of a Class 2 building or a Class 4 part of a building — for artificial … to the following: Emergency lighting provided in accordance with Part E4. E4, including dedicated light sources for photoluminescent exit signs required by S25C3(a). Signage, display lighting within cabinets and display cases that are … J7D3b, the following control devices must comply with Specification 40: Lighting timers. Motion detectors. Demand-operated controls. Daylight sensors and dynamic lighting control devices. Table J7D3a Maximum … 160 lx 4 Stairways, including fire-isolated stairways 2 Lift cars 3 5.5 Table Notes In areas not listed above, the maximum illumination … illumination power density adjustment factor in Table J7D3b and Table J7D3c and where the control device is not installed to comply with J6D4. J7D3c. Circulation spaces are included in the allowances listed in the Table. this table. Table J7D3b Illumination power density adjustment factor for a control device Item Notes 1 and 2 Description illumination power density adjustment factor Motion detector Demand-operated controls In a toilet or change room, other than a public toilet, in a Class 6 building 0.4 Motion detector Demand-operated controls Where a group of light fittings serving less than 100 m2 is controlled by one or more detectors 0.6 Motion detector Demand-operated controls Where a group of light fittings serving 100 m2 or … stepped switching of lights adjacent windows Notes 3 and 5 Se Serving a Class 3 or 9c building, or a Class 9a ward a

Removed words are struck through; added words are highlighted. Comparison of the text only.

Can't meet J7D3? A Performance Solution must meet the Performance Requirements it satisfies: J1P1, J1P2, J1P3, J1P4. Start a Performance Solution →