Deemed-to-Satisfy Provision · NCC 2022 Volume One

J7D6 Exterior artificial lighting

Part J7 Artificial lighting and power · NCC 2019: J6.5

Open J7D6 on NCC Online ↗

(1) Exterior artificial lighting attached to or directed at the facade of a building, must—

be controlled by—

a daylight sensor; or

a time switch that is capable of switching on and off electric power to the system at variable pre-programmed times and on variable pre-programmed days; and

when the total lighting load exceeds 100 W—

use LED luminaires for 90% of the total lighting load; or

be controlled by a motion detector in accordance with Specification 40; or

when used for decorative purposes, such as façade lighting or signage lighting, have a separate time switch in accordance with Specification 40.

(2) The requirements of (1)(b) do not apply to the following:

Emergency lighting in accordance with Part E4.

Lighting around a detention centre.

Changed in NCC 2025 (minor wording). See NCC 2025 Volume One J7D6, or show what changed.

(1) Exterior artificial lighting attached to or directed at the … of the total lighting load; or be controlled by a motion detector demand-operated control in accordance with Specification 40; or when used for decorative … in accordance with Part E4. Lighting around a detention centre.

Removed words are struck through; added words are highlighted. Comparison of the text only.

Can't meet J7D6? A Performance Solution must meet the Performance Requirements it satisfies: J1P1, J1P2, J1P3, J1P4. Start a Performance Solution →