NSW J8D3 Swimming pool heating and pumping

Part J8 Heated water supply and swimming pool and spa pool plant · varies J8D3 Swimming pool heating and pumping

Open on NCC Online ↗

Delete clause J8D3 and insert NSW J8D3 as follows:

(1) Heating for a swimming pool must be by—

a solar heater; or

a heater using reclaimed heat from another process such as reject heat from a refrigeration plant; or

a geothermal heater; or

a gas heater that—

if rated to consume 500 MJ/hour or less, achieves a minimum gross thermal efficiency of 86%; or

if rated to consume more than 500 MJ/hour, achieves a minimum gross thermal efficiency of 90%; or

a heat pump; or

a combination of (a) to (e).

(2) Where some or all of the heating required by (1) is by a gas heater or a heat pump, the swimming pool must have—

a cover with a minimum R-Value of 0.05; and

a time switch to control the operation of the heater.

(3) A time switch must be provided to control the operation of a circulation pump for a swimming pool.

(4) Where required, a time switch must be capable of switching electric power on and off at variable pre-programmed times and on variable pre-programmed days.

(5) Pipework carrying heated or chilled water for a swimming pool must comply with the insulation requirements of J6D9.

(6) For the purpose of J8D3, a swimming pool does not include a spa pool.

Applications

NSW J8D3 does not apply to a Class 2 building and a Class 4 part of a building.

Not in NCC 2025. No NSW J8D3 in NCC 2025 Volume One.