NSW J8D3 Swimming pool heating and pumping
Part J8 Heated water supply and swimming pool and spa pool plant · varies J8D3 Swimming pool heating and pumping
Delete clause J8D3 and insert NSW J8D3 as follows:
(1) Heating for a swimming pool must be by—
a solar heater; or
a heater using reclaimed heat from another process such as reject heat from a refrigeration plant; or
a geothermal heater; or
a gas heater that—
if rated to consume 500 MJ/hour or less, achieves a minimum gross thermal efficiency of 86%; or
if rated to consume more than 500 MJ/hour, achieves a minimum gross thermal efficiency of 90%; or
a heat pump; or
a combination of (a) to (e).
(2) Where some or all of the heating required by (1) is by a gas heater or a heat pump, the swimming pool must have—
a cover with a minimum R-Value of 0.05; and
a time switch to control the operation of the heater.
(3) A time switch must be provided to control the operation of a circulation pump for a swimming pool.
(4) Where required, a time switch must be capable of switching electric power on and off at variable pre-programmed times and on variable pre-programmed days.
(5) Pipework carrying heated or chilled water for a swimming pool must comply with the insulation requirements of J6D9.
(6) For the purpose of J8D3, a swimming pool does not include a spa pool.
Applications
NSW J8D3 does not apply to a Class 2 building and a Class 4 part of a building.