New South Wales variation · NCC 2022 Volume One

NSW S43C11 Supply of water for fire-fighting purposes

Specification 43 Bushfire protection for certain Class 9 buildings · varies S43C11 Supply of water for fire-fighting purposes

Open on NCC Online ↗

Delete clause S43C11 and insert NSW S43C11 as follows:

Water for fire-fighting purposes must be available and consist of—

A fire hydrant system complying with E1D2; or

A static water supply consisting of tanks, swimming pools, dams or the like, or a combination of these, together with suitable pumps, hoses and fittings, determined in consultation with the relevant fire brigade that—

is capable of providing the required flow rate for a period of not less than 4 hours; or

has a volume of 10 000 litres for each occupied building.

Same wording in NCC 2025 Volume One. See NCC 2025 Volume One NSW S43C11.