E1D2 Fire hydrants
Part E1 Fire fighting equipment · NCC 2019: E1.3
(1) A fire hydrant system must be provided to serve a building—
having a total floor area greater than 500 m2; and
where a fire brigade station is—
no more than 50 km from the building as measured along roads; and
equipped with equipment capable of utilising a fire hydrant.
(2) The fire hydrant system must be installed in accordance with AS 2419.1.
(3) Notwithstanding (2), a Class 8 electricity network substation need not comply with clause 4.2 of AS 2419.1 if—
it cannot be connected to a town main supply; and
one hour water storage is provided for fire-fighting.
(4) Where internal fire hydrants are provided, they must serve only the storey on which they are located except that a sole-occupancy unit—
in a Class 2 or 3 building or Class 4 part of a building may be served by a single fire hydrant located at the level of egress from that sole-occupancy unit; or
of not more than 2 storeys in a Class 5, 6, 7, 8 or 9 building may be served by a single fire hydrant located at the level of egress from that sole-occupancy unit provided the fire hydrant can provide coverage to the whole of the sole-occupancy unit.
Changed in NCC 2025. See NCC 2025 Volume One E1D2, or show what changed.
(1) A fire hydrant system must be provided to serve … The fire hydrant system must be installed in accordance with — AS 2419.1. 2419.1; or AS 2118.6, where applicable; or FPAA101H, where applicable. (3) Notwithstanding (2), — 2(a), a Class 8 electricity network substation need not comply with clause 4.2 4.1.2 of AS 2419.1 if — it cannot be connected to a town main supply; and one hour water storage is provided for fire-fighting. fire-fighting; and 2(b), plastic pipes and fittings must not be used above-ground in combined sprinkler and hydrant systems. (4) Where internal fire hydrants are provided, they must serve … can provide coverage to the whole of the sole-occupancy unit.