Northern Territory variation · NCC 2022 Volume One

NT F7D9 Walls between a bedroom and kitchen or laundry in a Class 9c building

NT Part F7 Sound transmission and insulation

Open on NCC Online ↗

In addition to NT F7D5, a wall separating a sole-occupancy unit in a Class 9c building from a kitchen or laundry must—

for other than masonry, be two or more separate leaves without rigid mechanical connection except at their periphery; or

be identical with a prototype that is no less resistant to the transmission of impact sound when tested in accordance with NT Specification 29 than a wall listed in NT S28C3.

Changed in NCC 2025. See NCC 2025 Volume One NT F7D9, or show what changed.

Insert NT clause F7D9 in clause F7D9 as follows: In addition to NT F7D5, a wall separating a sole-occupancy … NT Specification 29 than a wall listed in NT S28C3.