NCC 2022 Volume One
Specification 11 Smoke-proof walls in health-care and residential care buildings
4 clauses · Open on NCC Online ↗
- S11C1 ScopeThis Specification sets out requirements for the construction of smoke-proof walls in Class 9a health-care buildings and Class 9c buildings. (2)…
- S11C2 Class 9a health-care buildingsSmoke-proof walls required by C3D6 in Class 9a health-care buildings must comply with the following: Be non-combustible and extend to the underside…
- S11C3 Class 9c buildingsSmoke-proof walls required by C3D6 in Class 9c buildings must comply with the following: The wall may be lined on one side only. Linings on the wall…
- S11C4 Doorways in smoke-proof wallsA door required by C3D6 or this Specification to be smoke-proof or have an FRL, other than one that serves a fire compartment provided with a zone…