Specification clause · NCC 2022 Volume One

S11C3 Class 9c buildings

Specification 11 Smoke-proof walls in health-care and residential care buildings · NCC 2019: Spec C2.5: 3

Open S11C3 on NCC Online ↗

Smoke-proof walls required by C3D6 in Class 9c buildings must comply with the following:

The wall may be lined on one side only.

Linings on the wall must be non-combustible and extend to the underside of—

the floor above; or

a non-combustible roof covering; or

a flush plasterboard ceiling lined with 13 mm standard grade plasterboard or a fire-protective covering, with all penetrations sealed against the free passage of smoke.

If plasterboard is used in the lining on a wall, it must be a minimum of 13 mm standard grade plasterboard.

Not incorporate any glazed areas unless the glass is safety glass as defined in AS 1288.

Only have doorways which are fitted with smoke doors complying with Specification 12.

Have all openings around penetrations and the junctions of the smoke-proof wall and the remainder of the building stopped with non-combustible material to prevent the free passage of smoke.

Incorporate smoke dampers where air-handling ducts penetrate the wall unless the duct forms part of a smoke hazard management system required to continue air movement through the duct during a fire.

Changed in NCC 2025. See NCC 2025 Volume One S11C3, or show what changed.