Specification clause · NCC 2022 Volume One

S17C6 Sprinkler valve enclosures

Specification 17 Fire sprinkler systems · NCC 2019: Spec E1.5: 6

Open S17C6 on NCC Online ↗

(1) Sprinkler alarm valves must be located in a secure room or enclosure which has direct egress to a road or open space.

(2) All sprinkler valve rooms and enclosures must be secured with a system suitable for use by the fire brigade.

Same wording in NCC 2025 Volume One. See NCC 2025 Volume One S17C6.