Specification clause · NCC 2025 Volume One
S17C6 Sprinkler valve enclosures
Specification 17 Fire sprinkler systems · NCC 2019: Spec E1.5: 6
(1) Sprinkler alarm valves must be located in a secure room or enclosure which has direct egress to a road or open space.
(2) All sprinkler valve rooms and enclosures must be secured with a system suitable for use by the fire brigade.