Specification clause · NCC 2022 Volume One

S17C7 Water supply

Specification 17 Fire sprinkler systems · NCC 2019: Spec E1.5: 7

Open S17C7 on NCC Online ↗

(1) A required sprinkler system must be provided with at least one water supply.

(2) A required sprinkler system in a building greater than 25 m in effective height must be provided with a dual water supply except that a secondary water supply storage capacity of 25,000 litres may be used if—

the storage tank is located at the topmost storey of the building; and

the building occupancy is classified as no more hazardous than Ordinary Hazard 2 (OH2) under AS 2118.1; and

an operational fire brigade service is available to attend a building fire.

Same wording in NCC 2025 Volume One. See NCC 2025 Volume One S17C7.