S17C7 Water supply
Specification 17 Fire sprinkler systems · NCC 2019: Spec E1.5: 7
(1) A required sprinkler system must be provided with at least one water supply.
(2) A required sprinkler system in a building greater than 25 m in effective height must be provided with a dual water supply except that a secondary water supply storage capacity of 25,000 litres may be used if—
the storage tank is located at the topmost storey of the building; and
the building occupancy is classified as no more hazardous than Ordinary Hazard 2 (OH2) under AS 2118.1; and
an operational fire brigade service is available to attend a building fire.
Same wording in NCC 2022 Volume One. See NCC 2022 Volume One S17C7.