Specification clause · NCC 2022 Volume One

S19C4 Location of fire control centre

Specification 19 Fire control centres · NCC 2019: Spec E1.8: 3

Open S19C4 on NCC Online ↗

A fire control centre must be so located in a building that egress from any part of its floor, to a road or open space, does not involve changes in level which in aggregate exceed 300 mm.

Same wording in NCC 2025 Volume One. See NCC 2025 Volume One S19C4.