Specification clause · NCC 2022 Volume One
S19C4 Location of fire control centre
Specification 19 Fire control centres · NCC 2019: Spec E1.8: 3
A fire control centre must be so located in a building that egress from any part of its floor, to a road or open space, does not involve changes in level which in aggregate exceed 300 mm.