Specification 19 Fire control centres
13 clauses · Open on NCC Online ↗
- S19C1 ScopeThis Specification describes the construction and content of required fire control centres and rooms. (2) A fire control room is a fire control…
- S19C2 ApplicationS19C3 to S19C6 apply to fire control centres (including fire control rooms). (2) S19C7 to S19C13 apply additional requirements to fire control rooms.
- S19C3 Purpose and content of fire control centreA fire control centre must— provide an area from which fire-fighting operations or other emergency procedures can be directed or controlled; and…
- S19C4 Location of fire control centreA fire control centre must be so located in a building that egress from any part of its floor, to a road or open space, does not involve changes in…
- S19C5 Equipment not permitted within a fire control centreAn internal combustion engine, pumps, sprinkler control valves, pipes and pipe fittings must not be located in a fire control centre, but may be…
- S19C6 Ambient sound level for a fire control centreThe ambient sound level within the fire control centre measured when all fire safety equipment is operating in the manner in which it operates in an…
- S19C7 Construction of a fire control roomA fire control centre in a building more than 50 m in effective height must be in a separate room where— the enclosing construction is of concrete,…
- S19C8 Protection of openings in a fire control roomOpenings permitted by S19C7 must be protected as follows: Openings for windows, doorways, ventilation, service pipes, conduits and the like, in an…
- S19C9 Doors to a fire control roomRequired doors to a fire control room must open into the room, be lockable and located so that persons using escape routes from the building will…
- S19C10 Size and contents of a fire control roomA fire control room must contain— a Fire Indicator Panel and necessary control switches and visual status indication for all required fire pumps,…
- S19C11 Ventilation and power supply for a fire control roomA fire control room must be ventilated by— natural ventilation from a window or doorway in an external wall of the building which opens directly…
- S19C12 Sign for a fire control roomThe external face of the door to the fire control room must have a sign with the words— FIRE CONTROL ROOM in letters not less than 50 mm high and of…
- S19C13 Lighting for a fire control roomEmergency lighting in accordance with the Deemed-to-Satisfy Provisions of Part E4 must be provided in a fire control room, except that an…