Specification clause · NCC 2022 Volume One

S19C6 Ambient sound level for a fire control centre

Specification 19 Fire control centres · NCC 2019: Spec E1.8: 5

Open S19C6 on NCC Online ↗

(1) The ambient sound level within the fire control centre measured when all fire safety equipment is operating in the manner in which it operates in an emergency must not exceed 65 dB(A).

(2) The measurement must be taken for a sufficient time to characterise the effects of all sound sources.

(3) Where there is not a great variation in noise level, a measurement time of 60 seconds may be used.

Same wording in NCC 2025 Volume One. See NCC 2025 Volume One S19C6.