Specification clause · NCC 2022 Volume One

S19C7 Construction of a fire control room

Specification 19 Fire control centres · NCC 2019: Spec E1.8: 6

Open S19C7 on NCC Online ↗

A fire control centre in a building more than 50 m in effective height must be in a separate room where—

the enclosing construction is of concrete, masonry or the like, sufficiently impact resistant to withstand the impact of any likely falling debris, and with an FRL of not less than 120/120/120; and

any material used as a finish, surface, lining or the like within the room complies with the requirements of Specification 7; and

services, pipes, ducts and the like that are not directly required for the proper functioning of the fire control room do not pass through it; and

openings in the walls, floors or ceiling which separate the room from the interior of the building are confined to doorways, ventilation and other openings for services necessary for the proper functioning of the facility.

Same wording in NCC 2025 Volume One. See NCC 2025 Volume One S19C7.