Specification clause · NCC 2022 Volume One

S19C9 Doors to a fire control room

Specification 19 Fire control centres · NCC 2019: Spec E1.8: 8

Open S19C9 on NCC Online ↗

(1) Required doors to a fire control room must open into the room, be lockable and located so that persons using escape routes from the building will not obstruct or hinder access to the room.

(2) The fire control room must be accessible via two paths of travel—

one from the front entrance of the building; and

one direct from a public place or fire-isolated passageway which leads to a public place and has a door with an FRL of not less than –/120/30.

Same wording in NCC 2025 Volume One. See NCC 2025 Volume One S19C9.