Specification clause · NCC 2022 Volume One

S19C8 Protection of openings in a fire control room

Specification 19 Fire control centres · NCC 2019: Spec E1.8: 7

Open S19C8 on NCC Online ↗

Openings permitted by S19C7 must be protected as follows:

Openings for windows, doorways, ventilation, service pipes, conduits and the like, in an external wall of the building that faces a road or open space, must be protected in accordance with the Deemed-to-Satisfy Provisions of Part C4.

Openings in the floors, ceilings and internal walls enclosing a fire control room must, except for doorways, be protected in accordance with the Deemed-to-Satisfy Provisions of Part C4.

A door opening in the internal walls enclosing a fire-control room, must be fitted with a self-closing –/120/30 smoke sealed fire door.

Openings associated with natural or mechanical ventilation must—

not be made in any ceiling or floor immediately above or below the fire control room; and

be protected by a –/120/– fire damper if the opening is for a duct through a wall required to have an FRL, other than an external wall.

Same wording in NCC 2025 Volume One. See NCC 2025 Volume One S19C8.