S19C8 Protection of openings in a fire control room
Specification 19 Fire control centres · NCC 2019: Spec E1.8: 7
Openings permitted by S19C7 must be protected as follows:
Openings for windows, doorways, ventilation, service pipes, conduits and the like, in an external wall of the building that faces a road or open space, must be protected in accordance with the Deemed-to-Satisfy Provisions of Part C4.
Openings in the floors, ceilings and internal walls enclosing a fire control room must, except for doorways, be protected in accordance with the Deemed-to-Satisfy Provisions of Part C4.
A door opening in the internal walls enclosing a fire-control room, must be fitted with a self-closing –/120/30 smoke sealed fire door.
Openings associated with natural or mechanical ventilation must—
not be made in any ceiling or floor immediately above or below the fire control room; and
be protected by a –/120/– fire damper if the opening is for a duct through a wall required to have an FRL, other than an external wall.