Specification clause · NCC 2022 Volume One

S20C2 Type of system

Specification 20 Smoke detection and alarm systems · NCC 2019: Spec E2.2a: 2

Open S20C2 on NCC Online ↗

A required automatic smoke detection and alarm system must be provided in accordance with the following:

Class 2 buildings and Class 4 parts of a building—

a smoke alarm system complying with S20C3; or

a smoke detection system complying with S20C4; or

a combination of a smoke alarm system and a smoke detection system complying with S20C5.

Class 3 buildings—

with a Class 3 part located more than 2 storeys above ground level — a smoke detection system complying with S20C4; or

which accommodate more than 20 residents and are the residential part of a school, accommodation for the aged, children or people with a disability — a smoke detection system complying with S20C4; or

all other Class 3 buildings—

a smoke alarm system complying with S20C3; or

a smoke detection system complying with S20C4; or

a combination of a smoke alarm system and a smoke detection system complying with S20C5.

Class 5, 6, 7, 8, 9b and 9c buildings — a smoke detection system complying with S20C4

Class 9a health-care buildings—

where more than 6 bed patients are accommodated — a smoke detection system complying with S20C4; or

where 6 or less bed patients are accommodated—

a smoke alarm system complying with S20C3; or

a smoke detection system complying with S20C4.