S20C2 Type of system
Specification 20 Smoke detection and alarm systems · NCC 2019: Spec E2.2a: 2
A required automatic smoke detection and alarm system must be provided in accordance with the following:
Class 2 buildings and Class 4 parts of a building—
a smoke alarm system complying with S20C3; or
a smoke detection system complying with S20C4; or
a combination of a smoke alarm system and a smoke detection system complying with S20C5.
Class 3 buildings—
with a Class 3 part located more than 2 storeys above ground level — a smoke detection system complying with S20C4; or
which accommodate more than 20 residents and are the residential part of a school, accommodation for the aged, children or people with a disability — a smoke detection system complying with S20C4; or
all other Class 3 buildings—
a smoke alarm system complying with S20C3; or
a smoke detection system complying with S20C4; or
a combination of a smoke alarm system and a smoke detection system complying with S20C5.
Class 5, 6, 7, 8, 9b and 9c buildings — a smoke detection system complying with S20C4
Class 9a health-care buildings—
where more than 6 bed patients are accommodated — a smoke detection system complying with S20C4; or
where 6 or less bed patients are accommodated—
a smoke alarm system complying with S20C3; or
a smoke detection system complying with S20C4.
Clauses referred to
- S20C3 Smoke alarm system
- S20C4 Smoke detection system
- S20C5 Combined smoke alarm and smoke detection system