S20C3 Smoke alarm system
Specification 20 Smoke detection and alarm systems · NCC 2019: Spec E2.2a: 3
(1) In all Class 2 to 9 buildings provided with a smoke alarm system, the following applies:
A smoke alarm system must—
consist of smoke alarms complying with AS 3786; and
be powered from the consumer mains source.
In kitchens and other areas where the use of the area is likely to result in smoke alarms causing spurious signals, subject to (c)—
any other alarm deemed suitable in accordance with AS 1670.1 may be installed provided that smoke alarms are installed elsewhere in the sole-occupancy unit in accordance with (2)(a) and (2)(b); or
an alarm acknowledgement facility may be installed.
Where a kitchen or other area referred to in (b) is in a building protected with a sprinkler system complying with Specification 17 (other than a FPAA101D system), alarms need not be installed in the kitchen or other area likely to result in spurious signals.
(2) In a Class 2 or 3 building or Class 4 part of a building provided with a smoke alarm system, the following applies:
Alarms must be installed within each sole-occupancy unit, and located on or near the ceiling in any storey—
containing bedrooms—
between each part of the sole-occupancy unit containing bedrooms and the remainder of the sole-occupancy unit; and
where bedrooms are served by a hallway, in that hallway; and
not containing any bedrooms, in egress paths.
Where there is more than one alarm installed within a sole-occupancy unit, alarms must be interconnected within that sole-occupancy unit.
Subject to (d), alarms must be—
installed in public corridors and other internal public spaces, located in accordance with the requirements for smoke detectors in AS 1670.1; and
connected to activate a building occupant warning system in accordance with S20C7.
In a Class 2 or 3 building or Class 4 part of a building protected with a sprinkler system complying with Specification 17 (other than a FPAA101D system), alarms are not required in public corridors and other internal public spaces.
(3) In a Class 9a building provided with a smoke alarm system, smoke alarms must be—
installed in every room, public corridor and other internal public space; and
located in accordance with the requirements for smoke detectors in AS 1670.1; and
interconnected to provide a common alarm; and
have manual call points installed in evacuation routes so that no point on a floor is more than 30 m from a manual call point.