Specification clause · NCC 2022 Volume One

S20C4 Smoke detection system

Specification 20 Smoke detection and alarm systems · NCC 2019: Spec E2.2a: 4

Open S20C4 on NCC Online ↗
Varied in VIC. Check the variation for your state.

(1) In all Class 2 to 9 buildings provided with a smoke detection system, the following applies:

A smoke detection system must—

subject to (2), (3) and (4), comply with AS 1670.1; and

activate a building occupant warning system in accordance with S20C7.

In kitchens and other areas where the use of the area is likely to result in smoke detectors causing spurious signals, subject to (c)—

any other detector deemed suitable in accordance with AS 1670.1 may be installed provided that smoke detectors are installed elsewhere in the sole-occupancy unit in accordance with the requirements for alarms in S20C3(2)(a) and (2)(b); or

an alarm acknowledgement facility may be installed.

Where a kitchen or other area referred to in (b) is in a building protected with a sprinkler system complying with Specification 17 (other than a FPAA101D or FPAA101H system), detectors need not be installed in the kitchen or other areas likely to result in spurious signals.

(2) In a Class 2 or 3 building or Class 4 part of a building provided with a smoke detection system, the following applies:

Smoke detectors must be installed—

within each sole-occupancy unit, in accordance with the requirements for alarms in S20C3(2)(a) and (2)(b); and

subject to (b), in public corridors and other internal public spaces.

In a Class 2 or 3 building or Class 4 part of a building protected with a sprinkler system complying with Specification 17 (other than a FPAA101D or FPAA101H system), smoke detectors are not required in public corridors and other internal public spaces.

(3) In a Class 9a health-care building provided with a smoke detection system, the following applies:

Except as provided in (b)—

photoelectric type smoke detectors must be installed in patient care areas and in paths of travel to exits from patient care areas; and

in areas other than patient care areas and paths of travel to exits from patient care areas, where the use of the area is likely to result in smoke detectors causing spurious signals, any other detector deemed suitable in accordance with AS 1670.1 may be installed in lieu of smoke detectors.

The requirements of (a) do not apply where an area is protected with a sprinkler system complying with Specification 17, smoke detectors need not be installed where the use of the area is likely to result in spurious signals.

Manual call points must be installed in evacuation routes so that no point on a floor is more than 30 m from a manual call point.

(4) In a Class 9c building provided with a smoke detection system, the following applies:

remote automatic indication of each zone must be given in each smoke compartment by means of—

mimic panels with an illuminated display; or

annunciator panels with alpha numeric display; and

if the building accommodates more than 20 residents, manual call points must be installed in paths of travel so that no point on a floor is more than 30 m from a manual call point.

Same wording in NCC 2025 Volume One. See NCC 2025 Volume One S20C4.