S20C7 Building occupant warning system
Specification 20 Smoke detection and alarm systems · NCC 2019: Spec E2.2a: 7
Subject to E4D9, a building occupant warning system provided as part of a smoke hazard management system must comply with clause 3.22 of AS 1670.1 to sound through all occupied areas except—
in a Class 2 and 3 building or Class 4 part of a building provided with a smoke alarm system in accordance with S20C3(2)(c)—
the sound pressure level need not be measured within a sole-occupancy unit if a level of not less than 85 dB(A) is provided at the door providing access to the sole-occupancy unit; and
the inbuilt sounders of the smoke alarms may be used to wholly or partially meet the requirements; and
in a Class 2 and 3 building or Class 4 part of a building provided with a smoke detection system in accordance with S20C4(2), the sound pressure level from a building occupant warning system need not be measured within a sole-occupancy unit if a level of not less than 100 dB(A) is provided at the door providing access to the sole-occupancy unit; and
in a Class 3 building used as a residential care building, the system—
must be arranged to provide a warning for occupants; and
in areas used by residents, may have its alarm adjusted in volume and content to minimise trauma consistent with the type and condition of residents; and
in a Class 9a health-care building, in a patient care area, the system—
must be arranged to provide a warning for occupants; and
in a ward area, may have its alarm adjusted in volume and content to minimise trauma consistent with the type and condition of the patients; and
in a Class 9c building, the system—
must be arranged to provide a warning for occupants; and
must notify staff caring for the residents of the building; and
in areas used by residents, may have its alarm adjusted in volume and content to minimise trauma consistent with the type and condition of residents.
Changed in NCC 2025 (minor wording). See NCC 2025 Volume One S20C7, or show what changed.
Subject to E4D9, a building occupant warning system provided as part of a smoke hazard management system must comply with clause 3.22 3.17 of AS 1670.1 to sound through all occupied areas except … building provided with a smoke alarm system in accordance with S20C3(2)(c)— S20C3(2)(c) — the sound pressure level need not be measured within a … minimise trauma consistent with the type and condition of residents.