S31C12 Exhaust fans
Specification 31 Fire and smoke control systems in buildings containing atriums · NCC 2019: Spec G3.8: 3.6
(1) Smoke exhaust must be provided by fans capable of continuous and required operation for a period of not less than 1 hour when handling exhaust gases at 200°C.
(2) Where a Class 2, 3 or 9 part of a building adjoins an atrium, the atrium must be provided with a minimum of 3 fans each capable of 50% of the total required smoke exhaust capacity.
(3) Atriums other than those referred to in (2) must be provided with a minimum of 2 fans each capable of 50% of the total required smoke exhaust capacity.