NCC 2022 Volume One
Specification 31 Fire and smoke control systems in buildings containing atriums
20 clauses · Open on NCC Online ↗
- S31C1 ScopeThis Specification sets out the requirements for the design and operation of systems of fire and smoke control in buildings containing an atrium.
- S31C2 General requirement — automatic fire sprinkler systemA sprinkler system (other than a FPAA101D or FPAA101H system) complying with Specification 17 must be installed in every building containing an…
- S31C3 Roof protectionA roof of an atrium which does not have the FRL prescribed in Specification 5 or the Deemed-to-Satisfy Provisions of Part C3 must be protected by…
- S31C5 Sprinkler systems to glazed wallsWhere an atrium is separated from the remainder of the building by walls or doors incorporating glazing, a wall wetting system must be provided to…
- S31C6 Stop valvesBasic sprinkler and wall wetting systems protecting a building containing an atrium must be provided with easily accessible and identified stop…
- S31C7 General requirements — smoke control systemExcept where varied or superseded by this Specification, mechanical air-handling systems in a building containing an atrium must comply with AS…
- S31C8 Operation of atrium mechanical air-handling systemsMechanical air-handling systems serving an atrium must be designed to operate so that during a fire— a tenable atmosphere is maintained in all paths…
- S31C9 Activation of smoke control systemThe smoke control system must be activated by— operation of an automatic fire alarm; or operation of the sprinkler system; or a manual start switch.…
- S31C10 Smoke exhaust systemA smoke exhaust system serving an atrium must be designed on the basis of— the sprinkler system limiting the size of a fire to— a heat output of 1.5…
- S31C11 Upward air velocityNotwithstanding S31C10(c), the average upward air velocity in the atrium, due to the required smoke exhaust quantity must— be not less than 0.2 m/s…
- S31C12 Exhaust fansSmoke exhaust must be provided by fans capable of continuous and required operation for a period of not less than 1 hour when handling exhaust gases…
- S31C13 Smoke-and-heat ventsNotwithstanding S31C12, automatic vents complying with AS 2665 may be used, except where a Class 6 part of a building adjoins the atrium, in lieu of…
- S31C14 Make-up air supplyUniformly distributed make-up air must be provided to the atrium exhaust system from— outside the atrium at or near the lowest storey level; and…
- S31C15 General requirements—fire detection and alarm systemExcept where superseded by this Specification, automatic fire detection and alarm systems in a building containing an atrium must comply with AS…
- S31C16 Smoke detection systemSmoke detection within an atrium— must be provided within all outside air intakes and at individual floor return air intakes of all air-handling…
- S31C17 Smoke detection in spaces separated from the atrium by bounding wallsSmoke detection systems must be located at all return and relief air openings associated with the building air-handling systems and be— of the…
- S31C18 Alarm systemsA break-glass fire alarm point must be provided at each door to a fire-isolated stairway, fire-isolated ramp or fire-isolated passageway. (2) A…
- S31C19 Emergency warning and intercom systemsA building containing an atrium must be provided with an emergency warning and intercom system which— complies with AS 1670.4; and incorporates…
- S31C20 Standby power systemIf a required path of travel to an exit is within an atrium, a suitable alternative power supply must be provided to operate required safety…
- S31C21 System for excluding smoke from fire-isolated exitsRequired fire-isolated exits in a building containing an atrium must be protected from the entry of smoke in accordance with E2D3.