Specification clause · NCC 2022 Volume One

S31C16 Smoke detection system

Specification 31 Fire and smoke control systems in buildings containing atriums · NCC 2019: Spec G3.8: 4.2

Open S31C16 on NCC Online ↗

Smoke detection within an atrium—

must be provided within all outside air intakes and at individual floor return air intakes of all air-handling systems to initiate automatic fire mode operation, and where applicable, comply with the restart facilities in AS 1668.1; and

must operate at an obscuration level not greater than 0.5% per metre with compensation for external airborne contamination as necessary; and

must sample air within the atrium and in storeys where the bounding wall is set back more than 3.5 m from the atrium well; and

must be calibrated to compensate for smoke dilution where sampling occurs within return air path common to more than one room; and

may incorporate beam type detectors to sense smoke in an atrium in a Class 5, 6, 7 or 8 building with an effective height of not more than 25 m if the beam detectors are—

located at intervals of not more than 3 storeys; and

arranged to scan at 90 degrees orientation to adjacent beam units.

Same wording in NCC 2025 Volume One. See NCC 2025 Volume One S31C16.