S31C17 Smoke detection in spaces separated from the atrium by bounding walls
Specification 31 Fire and smoke control systems in buildings containing atriums · NCC 2019: Spec G3.8: 4.3
Smoke detection systems must be located at all return and relief air openings associated with the building air-handling systems and be—
of the sampling type system as required in S31C16; or
of the point type photoelectric smoke detector.