S31C3 Roof protection
Specification 31 Fire and smoke control systems in buildings containing atriums · NCC 2019: Spec G3.8: 2.2
(1) A roof of an atrium which does not have the FRL prescribed in Specification 5 or the Deemed-to-Satisfy Provisions of Part C3 must be protected by automatic sprinklers arranged to wet both the covering membrane and supporting structure if the roof is—
less than 12 m above the floor of the atrium or the floor of the highest storey where the bounding construction is set back more than 3.5 m from the atrium well if a Class 2, 3, 5 or 9 part of a building is open to the atrium; or
less than 20 m above the floor of the atrium or the floor of the highest storey where the bounding construction is set back more than 3.5 m from the atrium well if a Class 6, 7 or 8 part of a building is open to the atrium.
(2) The temperature rating of sprinkler heads required by (1) must be within the range 79°C – 100°C