Specification clause · NCC 2022 Volume One

S31C5 Sprinkler systems to glazed walls

Specification 31 Fire and smoke control systems in buildings containing atriums · NCC 2019: Spec G3.8: 2.4.1 – 2.4.5

Open S31C5 on NCC Online ↗

(1) Where an atrium is separated from the remainder of the building by walls or doors incorporating glazing, a wall wetting system must be provided to protect the glazing as follows:

On the atrium side of the glazing — to all glazed walls which are set back more than 3.5 m from the atrium well.

On the atrium side of the glazing — to all glazed walls which are not set back, or are set back 3.5 m or less, from the atrium well, for all levels which are less than—

12 m above the floor of an atrium or the floor of the highest storey where the bounding wall is set back more than 3.5 m from the atrium well if a Class 2, 3, 5 or 9 part of the building is open to the atrium; or

20 m above the floor of an atrium or the floor of the highest storey where the bounding wall is set back more than 3.5 m from the atrium well if a Class 6, 7 or 8 part of the building is open to the atrium.

On the side of the glazing away from the atrium well — to all glazing forming part of the bounding wall at each storey.

(2) Sprinklers must be located in positions allowing full wetting of the glazing surfaces without wetting adjacent sprinkler heads.

(3) Sprinkler heads must be of the quick response type and have a maximum temperature rating of 74°C.

(4) The rate of water discharge to protect glazing must be not less than—

on the atrium side of the glazing—

0.25 L/s.m2 where glazing is not set back from the atrium well; or

0.167 L/s.m2 where glazing is set back from the atrium well; and

on the side away from the atrium well — 0.167 L/s.m2.

(5) In addition to that of the basic sprinkler protection for the building, the water supply to required wall wetting systems must be of adequate capacity to accommodate the following on the atrium side of the glazing:

Where the bounding walls are set back less than 3.5 m from the atrium well — wall wetting of a part not less than 6 m long for a height of not less than—

12 m above the floor of an atrium or the floor of the highest storey where the bounding wall is set back more than 3.5 m from the atrium well if a Class 2, 3, 5 or 9 part of the building is open to the atrium; or

20 m above the floor of an atrium or the floor of the highest storey where the bounding wall is set back more than 3.5 m from the atrium well if a Class 6, 7 or 8 part of the building is open to the atrium.

Where the walls are set back 3.5 m or more from the atrium well — wetting of a part not less than 12 m long on one storey.

Same wording in NCC 2025 Volume One. See NCC 2025 Volume One S31C5.