Specification clause · NCC 2022 Volume One
S43C12 Emergency power supply
Specification 43 Bushfire protection for certain Class 9 buildings
(1) Emergency power must be provided to support, for not less than 4 hours before and 2 hours after the passing of the fire front during a bushfire event, the ongoing operation of—
air handling systems to maintain internal tenability; and
any pumps for fire-fighting; and
any emergency lighting and exit signs; and
any other emergency equipment listed in C3D14(6) and required to be provided.
(2) Manual control for emergency back-up power supply must be provided to facilitate manual intervention where the power supply fails or runs out.