Specification clause · NCC 2025 Volume One

S43C12 Emergency power supply

Specification 43 Bushfire protection for certain Class 9 buildings

Open S43C12 on NCC Online ↗

(1) Emergency power must be provided to support, for not less than 4 hours before and 2 hours after the passing of the fire front during a bushfire event, the ongoing operation of—

air handling systems to maintain internal tenability; and

any pumps for fire-fighting; and

any emergency lighting and exit signs; and

any other emergency equipment listed in C3D14(6) and required to be provided.

(2) Manual control for emergency back-up power supply must be provided to facilitate manual intervention where the power supply fails or runs out.

Same wording in NCC 2022 Volume One. See NCC 2022 Volume One S43C12.