Specification clause · NCC 2022 Volume One
S45C2 Reference building sole-occupancy unit
Specification 45 Modelling profiles for J1V5
The heating loads and cooling loads must be calculated for the reference building sole-occupancy unit in accordance with the following:
J3D7, for roofs.
J3D9, for wall-glazing construction.
J3D10, for floors.
J4D5, for roof lights.
Solar absorptance of 0.6 for external walls and roofs.
Open area of 3.8 x 10-4 m2 per m2 of zone façade area for façade air infiltration, separate to designed natural ventilation openings.
Not in NCC 2025. No S45C2 in NCC 2025 Volume One.