J3D7 Roofs and ceilings of a sole-occupancy unit of a Class 2 building or a Class 4 part of a building
(1) Roof and ceiling insulation must achieve the minimum R-Value—
in climate zone 1, in accordance with Tables J3D7a, J3D7b and J3D7c as applicable; and
in climate zone 2, in accordance with Tables J3D7d, J3D7e and J3D7f as applicable; and
in climate zone 3, in accordance with Tables J3D7g, J3D7h and J3D7i as applicable; and
in climate zone 4, in accordance with Tables J3D7j, J3D7k and J3D7l as applicable; and
in climate zone 5, in accordance with Tables J3D7m, J3D7n and J3D7o as applicable; and
in climate zone 6—
R3.5; or
if the roof contains reflective insulation, R3.0; and
in climate zones 7 and 8, in accordance with Tables J3D7p, J3D7q and J3D7r as applicable.
(2) Reflective insulation installed to comply with (1) must—
have a surface emittance of not more than 0.05; and
be adjacent to a roof space of not less than 20 mm; and
in climate zones 3 to 8, be downward facing.
(3) The thermal bridging in a metal-framed roof must be addressed as follows—
for a pitched roof with a horizontal ceiling—
achieving the Total R-Value in Table J3D7s, calculated using a method that accounts for the effects of thermal bridging; or
increasing the R-Value of the insulation between the ceiling frames by R0.5 more than the R-Value derived from (1); or
adding a continuous ceiling insulation layer with a minimum R-Value of R0.13 above or below the ceiling joists or the bottom chords of the trusses; or
achieving the required ceiling R-Value derived from (1) by stacking two layers of insulation immediately on top of each other, such that the top layer is orientated to cover the ceiling joists or bottom chord of the trusses and has an R-Value of at least R0.5; or
for a flat, skillion or cathedral roof—
achieving the Total R-Value in Table J3D7t, calculated using a method that accounts for the effects of thermal bridging; or
complying with Table J3D7u.
(4) Where F8D5(1) applies, continuous insulation placed above the primary insulation layer to mitigate thermal bridging must have a vapour permeance of not less than that of the primary insulation layer.
(5) Where, for operational or safety reasons, the area of ceiling insulation required is reduced, the loss of insulation must be compensated for in accordance with Table J3D7w.
(6) Where the ceiling insulation required by (1) to (5) has an R-Value—
greater than R3.0 and less than or equal to R4.5, it may be reduced to R3.0 within 450 mm of an external wall; or
greater than R4.5, it may be reduced to R3.0 within 450 mm of an external wall, provided all other required ceiling insulation is increased by R0.5.
(7) The requirements of (1) to (6) do not apply to roofs constructed using insulated sandwich panels.
(8) Roofs constructed using insulated sandwich panels must achieve the minimum Total R-Value in Table J3D7x.
(9) In climate zones 1 to 5, the solar absorptance of the upper surface of a roof must not be more than 0.64.
Table J3D7a Flat concrete roof — minimum R-Value for ceiling insulation: climate zone 1
Reflective insulation under-roof
SA ≤ 0.23
SA > 0.23 to ≤ 0.32
SA > 0.32 to ≤ 0.42
SA > 0.42 to ≤ 0.53
SA > 0.53 to ≤ 0.64
Yes
1.0
1.5
2.0
2.5
3.0
No
1.5
2.0
2.5
3.0
4.0
Table Notes
SA = solar absorptance.
The R-Value of reflective insulation is not to be included in the R-Value of any under-roof or ceiling insulation.
R-Values listed are for the labelled, declared R-Value of insulation.
Table J3D7b Timber-framed pitched roof with horizontal ceiling — minimum R-Value for ceiling insulation: climate zone 1
Roof ventilation
Reflective insulation under-roof
Under-roof insulation R-Value
SA ≤ 0.23
SA > 0.23 to ≤ 0.32
SA > 0.32 to ≤ 0.42
SA > 0.42 to ≤ 0.53
SA > 0.53 to ≤ 0.64
Vented
Yes
< 1.0
1.5
1.5
1.5
1.5
2.0
≥ 1.0 to < 1.5
1.5
1.5
1.5
1.5
1.5
≥ 1.5 to < 2.0
1.5
1.5
1.5
1.5
1.5
≥ 2.0
1.5
1.5
1.5
2.0
2.0
No
< 1.0
2.0
2.5
4.0
5.0
X
≥ 1.0 to < 1.5
1.5
1.5
1.5
1.5
2.5
≥ 1.5 to < 2.0
1.5
1.5
1.5
2.0
2.0
≥ 2.0
1.5
1.5
1.5
1.5
1.5
Standard
Yes
< 1.0
1.5
1.5
2.0
3.0
4.0
≥ 1.0 to < 1.5
1.5
1.5
1.5
1.5
2.5
≥ 1.5 to < 2.0
1.5
1.5
1.5
1.5
2.0
≥ 2.0
1.5
1.5
1.5
1.5
1.5
No
< 1.0
2.5
4.0
6.0
X
X
≥ 1.0 to < 1.5
1.5
1.5
1.5
1.5
4.0
≥ 1.5 to < 2.0
1.5
1.5
2.0
2.0
2.5
≥ 2.0
1.5
1.5
1.5
2.0
2.5
Table Notes
SA = solar absorptance.
A roof space is to be considered ‘vented’ if it—
has one wind-driven roof ventilator per 50 m2 of ceiling area with gable, eave or ridge vents; or
has one powered roof ventilator per 200 m2 of ceiling area with gable, eave or ridge vents; or
is a tiled roof without sarking-type material at roof level.
If a roof is not ‘vented’, it is a ‘standard’ roof.
The R-Value of reflective insulation is not to be included in the R-Value of any under-roof or ceiling insulation.
R-Values listed are for the labelled, declared R-Value of insulation.
X = not permitted.
Table J3D7c Timber-framed flat, skillion or cathedral roof — minimum R-Value for ceiling insulation: climate zone 1
Reflective insulation under-roof
SA ≤ 0.23
SA > 0.23 to ≤ 0.32
SA > 0.32 to ≤ 0.42
SA > 0.42 to ≤ 0.53
SA > 0.53 to ≤ 0.64
Yes
1.5
1.5
2.0
3.0
4.0
No
1.5
3.5
5.0
X
X
Table Notes
SA = solar absorptance.
The R-Value can be achieved by installing insulation under the roof or on top of the ceiling or a combination of both.
The R-Value of reflective insulation is not to be included in the R-Value of any under-roof or ceiling insulation.
R-Values listed are for the labelled, declared R-Value of insulation.
X = not permitted.
Table J3D7d Flat concrete roof — minimum R-Value for ceiling insulation: climate zone 2
Reflective insulation under-roof
SA ≤ 0.23
SA > 0.23 to ≤ 0.32
SA > 0.32 to ≤ 0.42
SA > 0.42 to ≤ 0.53
SA > 0.53 to ≤ 0.64
Yes
2.0
2.5
2.5
3.0
3.5
No
3.0
3.0
3.5
4.0
4.5
Table Notes
SA = solar absorptance.
The R-Value of reflective insulation is not to be included in the R-Value of any under-roof or ceiling insulation.
R-Values listed are for the labelled, declared R-Value of insulation.
Table J3D7e Timber-framed pitched roof with horizontal ceiling — minimum R-Value for ceiling insulation: climate zone 2
Roof ventilation
Reflective insulation under-roof
Under-roof insulation R-Value
SA ≤ 0.23
SA > 0.23 to ≤ 0.32
SA > 0.32 to ≤ 0.42
SA > 0.42 to ≤ 0.53
SA > 0.53 to ≤ 0.64
Vented
Yes
Any
2.5
No
0 to < 0.5
2.5
3.0
3.0
3.5
3.5
≥ 0.5
2.5
Standard
Yes
Any
2.5
No
0 to < 0.5
3.0
3.0
3.5
4.0
4.0
≥ 0.5 to < 1.0
2.5
2.5
2.5
3.0
3.0
≥ 1.0
2.5
Table Notes
SA = solar absorptance.
A roof is considered ‘vented’ if it—
has one wind-driven roof ventilator per 50 m2 of ceiling area with gable, eave or ridge vents; or
has one powered roof ventilator per 200 m2 of ceiling area with gable, eave or ridge vents; or
is a tiled roof without sarking-type material at roof level.
If a roof is not ‘vented’, it is a ‘standard’ roof.
The R-Value of reflective insulation is not to be included in the R-Value of any under-roof or ceiling insulation.
R-Values listed are for the labelled, declared R-Value of insulation.
Table J3D7f Timber-framed flat, skillion or cathedral roof — minimum R-Value for ceiling insulation: climate zone 2
Reflective insulation under-roof
SA ≤ 0.23
SA > 0.23 to ≤ 0.32
SA > 0.32 to ≤ 0.42
SA > 0.42 to ≤ 0.53
SA > 0.53 to ≤ 0.64
Yes
2.5
2.5
2.5
2.5
2.5
No
3.0
3.0
3.5
4.0
4.0
Table Notes
SA = solar absorptance.
The R-Value can be achieved by installing insulation under the roof or on top of the ceiling or a combination of both.
The R-Value of reflective insulation is not to be included in the R-Value of any under-roof or ceiling insulation.
R-Values listed are for the labelled, declared R-Value of insulation.
Table J3D7g Flat concrete roof — minimum R-Value for ceiling insulation: climate zone 3
Reflective insulation under-roof
SA ≤ 0.23
SA > 0.23 to ≤ 0.32
SA > 0.32 to ≤ 0.42
SA > 0.42 to ≤ 0.53
SA > 0.53 to ≤ 0.64
Yes
2.0
2.0
2.5
2.5
3.0
No
3.0
3.5
4.0
4.5
5.0
Table Notes
SA = solar absorptance.
The R-Value of reflective insulation is not to be included in the R-Value of any under-roof or ceiling insulation.
R-Values listed are for the labelled, declared R-Value
Tables
- Table J3D7a Flat concrete roof — minimum R-Value for ceiling insulation: climate zone 1
- Table J3D7b Timber-framed pitched roof with horizontal ceiling — minimum R-Value for ceiling insulation: climate zone 1
- Table J3D7c Timber-framed flat, skillion or cathedral roof — minimum R-Value for ceiling insulation: climate zone 1
- Table J3D7d Flat concrete roof — minimum R-Value for ceiling insulation: climate zone 2
- Table J3D7e Timber-framed pitched roof with horizontal ceiling — minimum R-Value for ceiling insulation: climate zone 2
- Table J3D7f Timber-framed flat, skillion or cathedral roof — minimum R-Value for ceiling insulation: climate zone 2
- Table J3D7g Flat concrete roof — minimum R-Value for ceiling insulation: climate zone 3
- Table J3D7h Timber-framed pitched roof with horizontal ceiling — minimum R-Values for ceiling insulation: climate zone 3
- Table J3D7i Timber-framed flat, skillion or cathedral roof — minimum R-Value for ceiling insulation: climate zone 3
- Table J3D7j Flat concrete roof — minimum R-Value for ceiling insulation: climate zone 4
- Table J3D7k Timber-framed pitched roof with horizontal ceiling — minimum R-Value for ceiling insulation: climate zone 4
- Table J3D7l Timber-framed flat, skillion or cathedral timber roof — minimum R-Value for ceiling insulation: climate zone 4
- Table J3D7m Flat concrete roof — minimum R-Value for ceiling insulation: climate zone 5
- Table J3D7n Timber-framed pitched roof with horizontal ceiling — minimum R-Value for ceiling insulation: climate zone 5
- Table J3D7o Timber-framed flat, skillion or cathedral roof — minimum R-Value for ceiling insulation: climate zone 5
- Table J3D7p Flat concrete roof — minimum R-Value for ceiling insulation: climate zones 7 and 8
- Table J3D7q Timber-framed pitched roof with flat ceiling — minimum R-Value for ceiling insulation: climate zones 7 and 8
- Table J3D7r Timber-framed flat, skillion or cathedral roof — minimum R-Value for ceiling insulation: climate zones 7 and 8
- Table J3D7s Metal-framed pitched roof with horizontal ceiling — minimum Total R-Value of ceiling to account for thermal bridging
- Table J3D7t Metal-framed flat, skillion or cathedral roof — minimum Total R-Value to account for thermal bridging
- Table J3D7u Metal-framed flat, skillion or cathedral roof – thermal bridging mitigation
- Table J3D7v Direction of heat flow
- Table J3D7w Adjusted minimum R-Value of ceiling insulation required to compensate for loss of ceiling insulation area
- Table J3D7x Total R-Values for roofs constructed with insulated sandwich panels
Changed in NCC 2025. See NCC 2025 Volume One J3D7, or show what changed.
(1) Roof and ceiling insulation must achieve the minimum R-Value … or ceiling insulation. R-Values listed are for the labelled, declared R-Value R-Val
Removed words are struck through; added words are highlighted. Comparison of the text only.