S5C8 Enclosure of shafts

Specification 5 Fire-resisting construction · NCC 2019: Spec C1.1: 2.7

Open S5C8 on NCC Online ↗

(1) Shaftsrequired to have an FRL must be enclosed at the top and bottom by construction having an FRL not less than that required for the walls of a non-loadbearing shaft in the same building.

(2) The provisions of (1) need not apply to—

the top of a shaft extending beyond the roof covering, other than one enclosing a fire-isolated stairway or ramp; or

the bottom of a shaft if it is non-combustible and laid directly on the ground.

Same wording in NCC 2025 Volume One. See NCC 2025 Volume One S5C8.