S5C7 Mezzanine floors: Concession

Specification 5 Fire-resisting construction · NCC 2019: Spec C1.1: 2.6

Open S5C7 on NCC Online ↗

(1) This Clause does not apply to a Class 9b building that is a spectator stand or audience viewing area accommodating more than 100 persons as calculated according to D2D18.

(2) A mezzanine and its supports need not have an FRL or be non-combustible provided—

the total floor area of all the mezzanines in the same room does not exceed 1/3 of the floor area of the room or 200 m2, whichever is the lesser; and

the FRL of each wall and column that supports any other part of the building within 6 m of the mezzanine is increased by the amount listed in Table S5C7.

Table S5C7 Increased FRLs — Construction surrounding mezzanines

Level otherwise required for any FRL criterion (mins)

Increase in level to not less than (mins)

30

60

60

90

90

120

120

180

180

240

Table Notes

The increase in level applies to each FRL criterion (structural adequacy, integrity or insulation) relevant to the building element concerned.

Tables

Same wording in NCC 2025 Volume One. See NCC 2025 Volume One S5C7.