South Australia variation · NCC 2022 Volume One

SA D2D4 When fire-isolated stairways and ramps are required

Part D2 Provision for escape · varies D2D4 When fire-isolated stairways and ramps are required

Open on NCC Online ↗

Delete subclause D2D4(2) and insert SA D2D4(2) as follows:

(2) Class 5, 6, 7, 8 or 9 buildings — Every stairway or ramp serving as a required exit must be fire-isolated unless—

in a Class 9a health-care building — it connects, or passes through or passes by not more than 2 consecutive storeys in areas other than patient care areas; or

it is part of an open spectator stand; or

in any other case except in a Class 9b early childhood centre or a Class 9c building, it connects, passes through or passes by not more than 2 consecutive storeys and one extra storey of any classification may be included if—

the building has a sprinkler system (other than a FPAA101D system) complying with Specification 17 installed throughout; or

the required exit does not provide access to or egress for, and is separated from, the extra storey by construction having—

an FRL of –/60/60, if non-loadbearing; and

an FRL of 90/90/90 for Type A construction or 60/60/60 for Type B or C construction, if loadbearing; and

no opening that could permit the passage of fire or smoke; or

it is a required exit from a bulk grain storage facility and there are no window or door openings within 3 m of the stairway, ramp or ladder.

Not in NCC 2025. No SA D2D4 in NCC 2025 Volume One.