D2D4 When fire-isolated stairways and ramps are required
Part D2 Provision for escape · NCC 2019: D1.3
(1) Class 2 and 3 buildings — The following applies:
Subject to (b), every stairway or ramp serving as a required exit must be fire-isolated unless it connects, passes through or passes by not more than—
3 consecutive storeys in a Class 2 building; or
2 consecutive storeys in a Class 3 building.
Notwithstanding (a), one extra storey of any classification may be included if—
it is only for the accommodation of motor vehicles or for other ancillary purposes; or
the building has a sprinkler system (other than a FPAA101D system) complying with Specification 17 installed throughout; or
the required exit does not provide access to or egress for, and is separated from, the extra storey by construction having—
an FRL of –/60/60, if non-loadbearing; and
an FRL of 90/90/90, if loadbearing; and
no opening that could permit the passage of fire or smoke.
(2) Class 5, 6, 7, 8 or 9 buildings — Every stairway or ramp serving as a required exit must be fire-isolated unless—
in a Class 9a health-care building — it connects, or passes through or passes by not more than 2 consecutive storeys in areas other than patient care areas; or
it is part of an open spectator stand; or
in any other case, except in a Class 9b early childhood centre or a Class 9c building, it connects, passes through or passes by not more than 2 consecutive storeys and one extra storey of any classification may be included if—
the building has a sprinkler system (other than a FPAA101D system) complying with Specification 17 installed throughout; or
the required exit does not provide access to or egress for, and is separated from, the extra storey by construction having—
an FRL of –/60/60, if non-loadbearing; and
an FRL of 90/90/90 for Type A construction or 60/60/60 for Type B or C construction, if loadbearing; and
no opening that could permit the passage of fire or smoke.
Exemptions
D2D4(2) does not apply to—
a Class 9b early childhood centre wholly within a storey that provides direct egress to a road or open space; or
a Class 9b early childhood centre with a rise in storeys of not more than 2, where the Class 9b early childhood centre is the only use in that building.