SA D2D6 Distance between alternative exits
Part D2 Provision for escape · varies D2D6 Distance between alternative exits
Delete clause D2D6 and insert SA D2D6 as follows:
Exits that are required as alternative means of egress must be—
distributed as uniformly as practicable within or around the storey served and in positions where unobstructed access to at least 2 exits is readily available from all points on the floor including lift lobby areas; and
not less than 9 m apart; and
not more than—
in a Class 2 or 3 building — 45 m apart; or
in a Class 9a health-care building, if such required exit serves a patient care area — 45 m apart; or
in all other cases — 60 m apart; and
located so that alternative paths of travel do not converge such that they become less than 6 m apart; and
notwithstanding (c), exits that are required as alternative means of egress in a farm building must not be more than 80 m apart.