Deemed-to-Satisfy Provision · NCC 2022 Volume One
D2D6 Distance between alternative exits
Part D2 Provision for escape · NCC 2019: SA D1.5(e), D1.5
Varied in SA. Check the variation for your state.
Exits that are required as alternative means of egress must be—
distributed as uniformly as practicable within or around the storey served and in positions where unobstructed access to at least 2 exits is readily available from all points on the floor including lift lobby areas; and
not less than 9 m apart; and
not more than—
in a Class 2 or 3 building — 45 m apart; or
in a Class 9a health-care building, if such required exit serves a patient care area — 45 m apart; or
in all other cases — 60 m apart; and
located so that alternative paths of travel do not converge such that they become less than 6 m apart.
Same wording in NCC 2025 Volume One. See NCC 2025 Volume One D2D6.
Can't meet D2D6? A Performance Solution must meet the Performance Requirements it satisfies: D1P1, D1P2, D1P3, D1P4, D1P5, D1P6, D1P8, D1P9. Start a Performance Solution →