South Australia variation · NCC 2022 Volume One

SA E1D14 Portable fire extinguishers

Part E1 Fire fighting equipment · varies E1D14 Portable fire extinguishers

Open on NCC Online ↗

Insert SA subclause E1D14(7) in clause E1D14 as follows:

(7) For Class A fire risks in a farm building the requirements of (1) need not be provided if—

portable fire extinguishers for Class A fire risks are provided in accordance with SA E1D14(8); or

notwithstanding the exemption provided by SA E1D3(1)(e), a fire hose reel system is provided in accordance with E1D3, or wash-down hoses or similar hoses that are—

not more than 36 m long; and

equipped with a spray nozzle suitable for fighting a fire at the incipient stage; and

permanently connected to a water supply which is sufficient to supply two hoses discharging at the rate of 20 litres per minute for 60 minutes; and

arranged to provide coverage to all points on the floor within.

Insert SA subclause E1D14(8) in clause E1D14 as follows:

(8) Portable fire extinguishers provided to comply with SA E1D14(7)(a) must be—

located at or adjacent to every required exit; or

in open walled farm buildings, one extinguisher is provided for every 500 m2 of floor area, or part thereof.

Not in NCC 2025. No SA E1D14 in NCC 2025 Volume One.

The national clause