Deemed-to-Satisfy Provision · NCC 2022 Volume One

E1D3 Fire hose reels

Part E1 Fire fighting equipment · NCC 2019: E1.4

Open E1D3 on NCC Online ↗
Varied in SA. Check the variation for your state.

(1) E1D3 does not apply to—

a Class 2, 3 or 5 building or Class 4 part of a building; or

a Class 8 electricity network substation; or

a Class 9c building; or

classrooms and associated corridors in a primary or secondary school.

(2) A fire hose reel system must be provided—

to serve the whole building where one or more internal fire hydrants are installed; or

where internal fire hydrants are not installed, to serve any fire compartment with a floor area greater than 500 m2.

(3) The fire hose reel system must—

have fire hose reels installed in accordance with AS 2441; and

provide fire hose reels to serve only the storey at which they are located, except a sole-occupancy unit of not more than 2 storeys in a Class 6, 7, 8 or 9 building may be served by a single fire hose reel located at the level of egress from that sole-occupancy unit provided the fire hose reel can provide coverage to the whole of the sole-occupancy unit.

(4) Fire hose reels must be located internally, externally or in combination, to achieve the system coverage specified in AS 2441.

(5) In achieving system coverage, one or a combination of the following criteria for individual internally located fire hose reels must be met in determining the layout of any fire hose reel system:

Fire hose reels must be located adjacent to an internal fire hydrant (other than one within a fire-isolated exit), except that a fire hose reel need not be located adjacent to every fire hydrant, provided system coverage can be achieved.

Fire hose reels must be located within 4 m of an exit, except that a fire hose reel need not be located adjacent to every exit, provided system coverage can be achieved.

Where system coverage is not achieved by compliance with (a) and (b), additional fire hose reels may be located in paths of travel to an exit to achieve the required coverage.

(6) Fire hose reels must be located so that the fire hose will not need to pass through doorways fitted with fire or smoke doors, except—

doorways in walls referred to in C3D6(1)(e) in a Class 9a building and C3D6(3)(d) in a Class 9c building, separating ancillary use areas of high potential fire hazard; and

doorways in walls referred to in C3D13 or C3D14 separating equipment or electrical supply systems; and

doorway openings to shafts referred to in C4D14.

(7) Where the normal water supply cannot achieve the flow and pressures required by AS 2441, or is unreliable—

a pump; or

water storage facility; or

both a pump and water storage facility,

must be installed to provide the minimum flow and pressures required by clause 6.1 of AS 2441.

Changed in NCC 2025. See NCC 2025 Volume One E1D3, or show what changed.

(1) E1D3 does not apply to — a Class 2, … or classrooms and associated corridors in a primary or secondary school. school; or areas less than 100m2 — which are separated from other parts of the building by construction having an FRL of not less than 60/60/60; and with any door in the construction required by (i) protected with a self-closing or automatic closing fire door having an FRL of not less than –/60/30; and which are provided with fire extinguishers in accordance with AS 2444 located on the egress side of an entry door to the space. (2) A fire hose reel system must be provided — … flow and pressures required by clause 6.1 of AS 2441.

Removed words are struck through; added words are highlighted. Comparison of the text only.

Can't meet E1D3? A Performance Solution must meet the Performance Requirements it satisfies: E1P1, E1P2, E1P3, E1P4, E1P5, E1P6. Start a Performance Solution →

State and territory variations all clauses side by side →

Clauses referred to

Defined terms used