South Australia variation · NCC 2022 Volume One

SA F4D6 Accessible unisex sanitary compartments

Part F4 Sanitary and other facilities · varies F4D6 Accessible unisex sanitary compartments

Open on NCC Online ↗

Delete subclause F4D6(1) and insert SA F4D6(1) as follows:

(1) Where required by F4D5(a), the minimum number of accessible unisex sanitary compartments for each Class of building is as follows:

For a Class 1b building—

not less than 1; and

where private accessible unisex sanitary compartments are provided for every accessible bedroom, common accessible unisex sanitary compartments need not be provided.

For a Class 2 building—

where sanitary compartments are provided in common areas, not less than 1; and

in every sole-occupancy unit required by SA D4D2(4) to be accessible, not less than 1.

For Class 3 and Class 9c buildings—

in every accessible sole-occupancy unit provided with sanitary compartments within the accessible sole-occupancy unit, not less than 1; and

at each bank of sanitary compartments containing male and female sanitary compartments provided in common areas, not less than 1.

For Class 5, 6, 7, 8 or 9 buildings except for within a ward area of a Class 9a health-care building, where F4D4 requires closet pans—

1 on every storey containing sanitary compartments; and

where a storey has more than 1 bank of sanitary compartments containing male and female sanitary compartments, at not less than 50% of those banks.

For a Class 10a building appurtenant to another Class of building, at each bank of sanitary compartments containing male and female sanitary compartments, not less than 1.

Same wording in NCC 2025 Volume One. See NCC 2025 Volume One SA F4D6.